Industrial Exhaust Ventilation for Workplace Contaminant Control
Heavent program features
and included additional software and manual
The Heavent program can be used to design new systems, redesign or balance installed systems, to aid in commissioning recently installed systems, and to troubleshoot long-installed systems.

Back to main site /Ordering Heavent / Windows Upgrade / Download demo / Screen shots


Components of the Heavent Software Package 

Main Program
HEAVENT
Program Manual
Auxiliary Programs in the Heavent Package
HV_MEASUREMENT
DILUTION
CALIBRATE
Design, balancing and redesign of ventilation systems

Covers use of Heavent & use of the auxiliary programs

Measurement of pressures and flows in the field & troubleshooting

Dilution ventilation using the one-cell mass-balance model

Calibration of pressure measuring devices

 

Return to top of page / Back to main site

 

New system design features

Aspect of design

Features for new design

Limitations

Schematic/ Duct layout
  • Layout done quickly and easily on a simple schematic of the system
  • Can generate many simple systems in three mouse clicks
  • Allows system of any complexity
  • Detemines for itself whether a duct is a branch, submain, or main and whether it is part of a subsystem.
  • Simple to change layout: just change the schematic
    Layout can be changed at any time without re-inputting other information (program automatically re-computes based on the new layout)
  • Allows two laterals on a junction fitting (a real boon to rational layout)
  • It is so fast and simple that ex-users of competing programs are sometimes confused because they "couldn't believe it was that easy".
1) It is a schematic, not a scale drawing
2) cannot be printed as graphics image

Hood airflow
Computes suggested airflows for common simple hood designs (e.g., table-top capturing hoods and enclosing hoods) using the author's best guess of the effects of toxicity, exposure conditions, cross-draft velocity, and distance of the source from the hood and from the person protected by the hood many of the recommendations are based on "educated guesses" since published research offers little guidance

Duct sizing
  • Allows use of round, rectangular, or flat oval ducts
  • Selects intial round duct sizes from user-editable files of available duct sizes
  • Allows user to over-ride program choices
  • Can display duct dimensions on schematic
  • Makes optimal re-sizing relatively easy (see Optimization)
1) diameters < 12.1 ft
2) up to 100 sizes on a list
3) automatic sizing for round ducts, only

Static pressure calculations
  • Extensive user-editable defaults drastically reduce number of required inputs
  • Loss coefficients choices shown when and where needed. Progam computes many for itself based on simple user inputs.
  • Entire run of ducts described at once (e.g., number of 90 degree elbows in this branch), which is much faster than describing each and every component individually as other programs require
  • Pressures and flows re-computed instantly with every input you make, giving helpful feedback on effects of design choices
  • Makes psychrometrics easy. Requires only that you input the dry bulb temperature and one other parameter (e.g., relative humidity). Elevation effects done automatically (table of elevations for most U.S. cities included)
  • All computations done the most robust way possible -- not by using the approximations necessary for hand calculations.
  • The pressures computed are what you should expect to measure in the system. Oddly enough, the values computed in manuals, text books, and other programs are not. They fail to correct for the complex interactions between branch pressure requirements and are computed for locations that are inimical to accurate measurements.
 

Optimization

The schematic can display several parameters that are helpful in optimizing system design. The most important are Percentage of Ideal Airflow and Percentage of Target Velocity. The values appear as a label on each duct on the schematic, giving a easily understood view of which ducts should be re-sized or otherwise modified.
Just as importantly, it is so easy to make changes to the system that you can quickly try a change, then look at the flow at the fan and see if your change was a good idea. If not, change it back. It takes only a few key strokes or mouse clicks, so just try different combinations until you are completely satisfied you have done the best that can be done (i.e., ideal airflow at the fan approaches 100%).

In that regard, note that the author's damper balancing procedure produces the least possible energy costs and involves the least possible time to adjust dampers (second rounds rarely necessary)

 

Fan calculations
Computes FanSP and FanTP properly corrected for air density
Simplifies computation of effects of poor inlet and outlet condition on fan performance
Limitation: one main fan allowed per system (but does allow "booster fans" on ducts)
 

List of materials
lists numbers of 15, 30, 45, 60, and 90 degree elbows for each combination of duct diameter, duct roughness, and duct gauge.
lists total length of straight duct for each combination of diameter, duct roughness, and duct gauge
 

Return to top of page / Back to main site


 

Testing new systems
Return to top of page / Back to main site

Time


Note that these procedures do not require that the fan be running at the correct speed and both have little difficulty in separating out multiple problems in the system.

Quick
You compute system pressures on "as installed" system in design mode
2) Program predicts ratio of hood static pressure (SPH) to pressure at the end of the duct (SPend) for each branch duct.
3) You measure SPH and SPend for each branch in the installed system.
4) You compare ratio of measured values to predicted ratio for each branch
5) A deviation greater than 15% indicates a substantial deviation from expected values
Does not consider substantial deviations in ducts other than branches.

Thorough
Same as "Quick", except that you measure SPend for every duct in the system and do a Pitot traverse on each branch (the Hv_meas data acquisition program can speed that up enormously).
2) Heavent computes the equivalent loss coefficient for each duct and compares it to its expected value.
3) A deviation greater than 30% indicates a substantial deviation from expected values that warrants close inspection. First, you should review tables of inputed information (diameter, number of elbows, etc.) and visually compare to the installed duct. If that checks out, you should consider viewing the inside of the duct with a borescope or by disconnecting it.
4) If the deviations at the fan inlet and outlet are large, then fan performance will be affected. Conversely, if they are small, then deviations from expected airflow from the fan are due to the fan or its inlet or outlet conditions.

Return to top of page / Back to main site

Redesigning or re-balancing installed systems to meet current needs

Topic

Procedure

Redesign
Using Heavent, create a schematic of the system that matches your sketch of the system.
2) Using Hv_meas (an included DOS program), you measure hood static pressure (SPH) and complete a Pitot traverse for each branch and measure SPend for each duct in the installed system.
3) Import Hv_meas file into Heavent
4) In Heavent, input the correct duct length, number of elbows, and roughness for each duct you may wish to alter. For example, if you want to remove and elbow and 10 ft of duct from branch 3, you must enter the length and roughness of the duct and the number of elbows in it.
5) Make any changes to the system you wish.
6) Looking at the predicted effects on the system, tweak the system for optimal performance by changing duct diameters as needed. If a substantial fraction of ducts must be replaced, you should consider rebuilding the system from scratch.

Balancing with dampers

First 3 steps same as "Redesign" above.
In Heavent, set to "balance with dampers."
3) Input the new airflows you would like to see in each hood.
4) Heavent predicts ratio of hood static pressure to pressure at the end of the duct (SPH/SPend) that will exist if the dampers are each adjusted correctly.
5) Adjusting dampers in the field: Adjust each damper in turn until the observed value of SPH/SPend is nearly the same as the predicted ratio. One round of adjustements should be sufficient.
6) Measure airflow at fan inlet, then adjust fan rotation rate (w) so that:

Note: this procedure should give the best possible distribution at the lowest possible energy use and take far less time than other methods.

 


Manual
Over 200 pages of guidance, step-by-step procedures for common problems, and example problems. All input and design choices are explained -- including the ventilation issues behind them.
Section
Title of Section_______________________________

I

Installation

II

Heavent Screens

III

Procedures
IV
Step by Step Detailed Solution of an Example Problem
V
Use of Hv_Meas, a DOS program
VI
Use of Dilution, a DOS program

 

 


Additional DOS applications
(note: all programs toggle freely between S.I. and inch-pound units)
 Included

Purpose of each component of the software package

Hv_cal

 Aids in calibrating digital pressure manometers.

 Dilution
 Aids in dilution ventilation calculations employing the commonly used one-cell, mass-balance model (which is seriously flawed but usually much better than guessing).

Manual

The auxiliary programs are explained in Heavent Manual.


Return to top of page / Back to main site /Ordering Heavent / Windows Upgrade / Download demo / Screen shots

 Steven E. Guffey, PhD, CIH
1403 Far Meadows
Morgantown, WV 26508
ph: (304) 293-4607 x 3707
Internet: seguffey@gmail.com