|
Industrial
Exhaust Ventilation for Workplace Contaminant Control Heavent program features and included additional software and manual The Heavent program can be used to design new systems, redesign or balance installed systems, to aid in commissioning recently installed systems, and to troubleshoot long-installed systems. |
Back to main site /Ordering Heavent / Windows Upgrade / Download demo / Screen shots
Components of the Heavent Software Package
| Main
Program HEAVENT |
Program
Manual |
Auxiliary
Programs in the Heavent Package |
||
| HV_MEASUREMENT |
DILUTION
|
CALIBRATE |
||
| Design,
balancing and redesign of ventilation systems |
Covers use of Heavent & use of the auxiliary programs |
Measurement of pressures and flows in the field & troubleshooting |
Dilution
ventilation using the one-cell mass-balance model |
Calibration of pressure measuring devices |
|
|
|
|
|
|
|
1) It is a schematic, not
a scale drawing 2) cannot be printed as graphics image |
|
|
Computes suggested airflows for common simple hood designs (e.g., table-top capturing hoods and enclosing hoods) using the author's best guess of the effects of toxicity, exposure conditions, cross-draft velocity, and distance of the source from the hood and from the person protected by the hood | many of the recommendations are based on "educated guesses" since published research offers little guidance |
|
|
|
1) diameters < 12.1 ft 2) up to 100 sizes on a list 3) automatic sizing for round ducts, only |
|
|
|
|
|
|
The schematic can display several
parameters that are helpful in optimizing system design. The most important
are Percentage of Ideal Airflow and Percentage of Target Velocity. The
values appear as a label on each duct on the schematic, giving a easily
understood view of which ducts should be re-sized or otherwise modified. In that regard, note that the author's damper balancing procedure produces the least possible energy costs and involves the least possible time to adjust dampers (second rounds rarely necessary) |
|
|
|
Computes FanSP and FanTP properly
corrected for air density Simplifies computation of effects of poor inlet and outlet condition on fan performance Limitation: one main fan allowed per system (but does allow "booster fans" on ducts) |
|
|
|
lists numbers of 15, 30,
45, 60, and 90 degree elbows for each combination of duct diameter, duct
roughness, and duct gauge. lists total length of straight duct for each combination of diameter, duct roughness, and duct gauge |
|
|
Note that these procedures do not require that the fan be running at the correct speed and both have little difficulty in separating out multiple problems in the system. |
|
|
You compute system pressures on "as
installed" system in design mode 2) Program predicts ratio of hood static pressure (SPH) to pressure at the end of the duct (SPend) for each branch duct. 3) You measure SPH and SPend for each branch in the installed system. 4) You compare ratio of measured values to predicted ratio for each branch 5) A deviation greater than 15% indicates a substantial deviation from expected values Does not consider substantial deviations in ducts other than branches. |
|
|
Same as "Quick", except
that you measure SPend for every duct in the system and do a Pitot traverse
on each branch (the Hv_meas data acquisition program can speed that up
enormously). 2) Heavent computes the equivalent loss coefficient for each duct and compares it to its expected value. 3) A deviation greater than 30% indicates a substantial deviation from expected values that warrants close inspection. First, you should review tables of inputed information (diameter, number of elbows, etc.) and visually compare to the installed duct. If that checks out, you should consider viewing the inside of the duct with a borescope or by disconnecting it. 4) If the deviations at the fan inlet and outlet are large, then fan performance will be affected. Conversely, if they are small, then deviations from expected airflow from the fan are due to the fan or its inlet or outlet conditions. |
|
|
|
|
|
Using Heavent, create a schematic
of the system that matches your sketch of the system. 2) Using Hv_meas (an included DOS program), you measure hood static pressure (SPH) and complete a Pitot traverse for each branch and measure SPend for each duct in the installed system. 3) Import Hv_meas file into Heavent 4) In Heavent, input the correct duct length, number of elbows, and roughness for each duct you may wish to alter. For example, if you want to remove and elbow and 10 ft of duct from branch 3, you must enter the length and roughness of the duct and the number of elbows in it. 5) Make any changes to the system you wish. 6) Looking at the predicted effects on the system, tweak the system for optimal performance by changing duct diameters as needed. If a substantial fraction of ducts must be replaced, you should consider rebuilding the system from scratch. |
|
|
First 3 steps same as "Redesign"
above. Note: this procedure should give the best possible distribution at the lowest possible energy use and take far less time than other methods. |
| Included
|
Purpose of each component of the software package
|
|
|
|
|
|
Aids in dilution ventilation calculations employing the commonly used one-cell, mass-balance model (which is seriously flawed but usually much better than guessing). |
|
|
The auxiliary programs are explained in Heavent Manual. |
Return to top of page / Back to main site /Ordering Heavent / Windows Upgrade / Download demo / Screen shots
|
1403 Far Meadows Morgantown, WV 26508 ph: (304) 293-4607 x 3707 Internet: seguffey@gmail.com |